Nfpa 13 specifies how to properly design and install a sprinkler system using the proper components and materials after it has been determined that a sprinkler system is required.
Draft curtain nfpa 13.
20 6 6 6 3 20 6 5 3 3 a clear aisle of at least 4 ft 1 2 m centered below the draft curtain shall.
Draft curtains are also required by nfpa 13 in buildings where an early suppression fast response esfr is adjacent to standard response systems.
See our fire protective smoke curtains in action.
Nfpa 13 requires closely spaced sprinklers with a draft curtain around unenclosed moving stairways staircases or similar unenclosed floor openings which are not large 20 feet or more across and 1000 sqft or greater as an alternative to the enclosure of the vertical opening nfpa 13 8 15 4 1 in 2016 and 9 3 5 1 in 2019.
The maximum projected floor area under an individual sprinkler system shall be in accordance with chapters 6 and 7.
5 17 3 draft curtain areas shall be around each roof ceiling fire suppression system and subdivided such that a single draft curtain area shall not exceed 697 m2 7500 ft2.
According to nfpa 13 draft curtains need to be 2 feet deep but the ibc code commentary refers to 18.
Smoke fire on vimeo.
Draft curtains paragraph 3 3 8 draft curtain of nfpa 13 2016 standard for the installation of sprinkler systems defines draft curtains as a continuous material protruding downward from the ceiling to create a reservoir for collecting smoke and heat it references nfpa 204 2015 standard for smoke and heat venting for additional information.